Products | Earth Resistance Testers | TELARIS® EARTH-TEST

TELARIS® EARTH-TEST


TELARIS®_EARTH-TEST Technical data
Display 3 digit; LCD; 1999 Count
Meas. Principle Current-voltage measurement
Earth Resistance 0.05...19.99 Ω / 0.01 Ω; 20...199.9 Ω / 0.1 Ω; 200...1999 Ω / 1 Ω
Tolerance ±(4% rdg.+2 Digits / 0.1Ω)
Probe/aux. resistance 0.1...50 kΩ / 0.1 kΩ
Tolerance ±(10% rdg.+3Digits)
Test Current Display 0.1...13 mA / 0.1 mA
Tolerance ±(10% rdg.+3 Digits)
Max. Test Current approx. 12 mA
Test Voltage max. 25 V / 50 V AC selectable
Frequency 127 Hz / 140 Hz selectable
Safety Complying with IEC61010/EN61010/DIN VDE 0411, IEC61557/EN61557/DIN VDE 0413
Overvoltage category CAT III / 300 V
Pollution Degree 2
Power Supply 6 x 1.5 V, IEC LR6
Dimensions 235 x 105 x 70 mm
Weight approx. 640 g
Quick-Links
Order Documents
NEW AT-Series Underground Cable Locators
NEW! Mini Infrared Thermometer IR-500